ST Strainers (52bar)

These rugged Strainers (Filters) are specifically designed to facilitate the removal of foreign materials from refrigeration systems. Strainers help prevent damage to valves and other components, thereby reducing costly service and downtime. They can also be installed as a separate unit. They are available in 1/2" to 6" (13 mm to 150 mm) sizes.

Service & Maintenance

Repeated inspection of strainers during system startup or repairs is essential for optimum benefit. Before opening a strainer or any other component, be sure it is isolated from the system, and all refrigerant is removed (pumped out to zero pressure). The 1/2” through 2” strainers have a drain plug in the bottom cover for connecting a drain valve and hose for proper and safe removal of any trapped liquid refrigerant.

Screen Removal and Cleaning: Be careful to avoid any refrigerant which may still be in the strainer. Loosen the bottom cover bolts and bottom cover, check for refrigerant presence, and then remove the bolts, cover, and screen assembly. Clean the screen assembly with a good solvent, blow dry, and inspect. If the screen is damaged or sediment cannot be removed from the screen, replace the screen assembly. Carefully align the screen assembly in the center of the strainer body and replace the bottom cover. Pressure test for leaks before returning to service.

MATERIAL SPECS

Body: 1/2” through 1”: Forged Steel ASTM A350 Grade LF2 2”: Cast Steel ASTM A352 Grade LCB
Bottom Cover: Steel Plate for Low Temperature
Drain Plug: 1/4” NPT Standard
Screen: Stainless steel, 60 mesh (233 micron rating) or 100 mesh (150 micron rating)
Gaskets: Nonasbestos, graphite composite
Safe Working Pressure: 754 psig (52 bar)
Operating Temperature: –60°F to +240°F (–50ºC to +115°C)